Capacity |
Number |
- Up to 20 optional PCI ExpressModules.
- Up to 4 optional PCI Express Network Express Modules (NEM).
- Up to 10 hot-pluggable Sun Blade Server Modules.
- 6, 3000-Watt, grid redundant power supplies; up to 735W budgeted per blade; 9000W total system power.
- 3 fan modules to cool the PCI Express ExpressModules.
- Up to 2 redundant Chassis Monitoring Modules with failover capability.
- 9 high-performance fans to cool the blades.
- 160 Gbps of I/O throughput via PCIe lanes to the midplane
|
Management Environment
The Sun Blade 8000 Modular System has a tiered system management architecture that allows management
at either the chassis level or the Server Module level.
|
Common System Management for both the Chassis and the Server Module |
- Integrated Lights Out Management (ILOM) 1.1 with RKVMS (Remote Keyboard Video Mouse) is pre-installed on the CMM and the SP. ILOM will run on standby power.
Note: Accessing ILOM through Mozilla will require Mozilla version 1.7.5 or greater.
- Support for Sun N1 System Manager 1.3.1.
- Compatibility for third-party SNMP system managers with requirements for SNMP (v1, v2C, v3) and IPMI (2.0).
- System management is consistent with Sun Fire X4100 and Sun Fire X4200 servers.
|
Sun Blade 8000 Chassis Monitoring Module (CMM) |
- For redundancy, a second CMM is optional.
- 1 RJ-45 dedicated management network 100BaseT port for Secure Shell CLI to ILOM,
web GUI access to ILOM, IPMI 2.0, and SNMP v1, v2C, and V3.
- A DB-9 serial port to access ILOM CLI.
- 1 RJ-45 AUX port is currently not functional.
- The CMM's network ports are independent and do not interfere with network data traffic on, for example, a Network Express Module (NEM) communication option.
- Connections to CMM's Serial Management (DB-9 SERIAL MGT) port:
- Laptop USB to SERIAL MGT port via serial null modem or cross over cable.
- Network to Dongle DB9F to RJ45F, DCE Adapter (part number 530-3813 ships with chassis) to SERIAL MGT port.
- Managing through the CMM does allow Server Module level management.
|
Power
Supplies |
Number |
Six, hot-plug / hot-swap, high-efficiency(~87%) power supplies are provided in a 3+3 redundant configuration.
|
Output |
3000 W per power supply |
Standard Integrated Interfaces |
Network |
The Sun Blade 8000, without an optional EM or NEM, does not offer network or I/O connectivity.
|
Network Management |
The CMM provides one RJ-45 100BaseT port and a DB-9 Serial Management port, the Server Module provides a DB-9 serial port. Reference the Management Environment section.
|
PCI Interfaces |
The Sun Blade 8000 Modular System I/O is architected using PCI Express technology with total I/O output of 1,920 Gbps when fully populated with 10 Server Modules. The Sun Blade 8000 chassis can support:
Up to two optional I/O PCI Express ExpressModules (EMs)
and
Up to four Network Express Modules (NEMs)
|
USB |
Each optional Server Module provides two USB 2.0 ports.
|
Video |
Each optional Server Module provides a VGA Video connection to the ATI Rage XL graphics chip. |
Environment |
AC input |
- Voltage: 200-240 VAC
- Frequency: 50-60 Hz
- Current: 16A per AC input
- Number of AC Inputs: 6
- Maximum in-rush current: 40A
- Power Factor: 0.98
|
Input power |
AC input connection:
- AMER- L6-20P to IEC 320 C19; 2.5m; Sun PN 180-2005-01
- EPAC- IEC 309 to IEC 320 320 C19; 2.5m; Sun PN 180-2004-01
- Preinstalled in rack with power distribution unit - IEC 320 C20 to IEC 320 C19
|
Heat output |
Thermal Design:
- Total system volumetric airflow (front to rear): 1500 (Cubic Feet per Minute)
- Airflow direction: Front to back
- Total heat dissipation / HVAC load: 30,735 BTU/hr (assuming 9,000W)
- Average temperature rise through chassis: 15° C (59° F)
|
Temperature |
Operating: 5°C to 35°C (41° F to 95° F)
Nonoperating: -40°C to 65°C (-40° F to 149° F) |
Relative Humidity |
Operating: 10% to 90% RH, non-condensing, 27° C max wet bulb
Nonoperating: 5% to 93% RH, non-condensing, 38° C max wet bulb |
Altitude |
0 to 7,500 feet (2,286m) |
Regulations
Meets or exceeds the following requirements: |
RoHS Compliance Level |
RoHS:YL |
Product Safety |
- UL approved to UL 60950 and C22.2 No. 60950
- TUV approved to EN60950-1 and CB Report IEC 950 3rd Edition; including all amendments and full worldwide deviations
- GOST Certification
- Korean MIC Certification
- China CCC Mark for power supply only (system is exempt since it is rated greater than 1300W)
- CE Declaration of Conformance to the Electronic Compatibility Directive and Low Voltage Directive with accompanying "Technical Data
File"
-
- Approval to Argentinian standards
|
Laser Product and Optical I/O |
- FCC Regulation to Code of Federal regulations 21 CFR 1040-Lasers
- TUV approval to IEC 60825-1 Safety of Laser Products
- Canadian Radiation Emitting Devices Act REDR C1370
|
Emissions and Immunities: |
Electromagnetic Interference |
- 47 CFR 15B (Code of Federal Regulations, Part 15, Subpart B) Class A
- EN55022:1998 Class A per EMC directive 89/336/EEC (CE Mark)
- VCCI Class A
- Industry Canada ICES-003
- AS/NZ 3548 (Australia/New Zealand)
- CNS 13438 (Taiwan)
|
Immunity |
- EN55024:1998 per EMC Directive 89/336/EEC
- IEC 61000-4-2 Electrostatic discharge immunity test
- IEC 61000-4-3 Radiated, radio-frequency, electromagnetic field immunity test
- IEC 61000-4-4 Electrical fast transient/burst immunity test
- IEC 61000-4-5 Surge immunity test
- IEC 61000-4-6 Immunity to conducted disturbances, induced by radio-frequency fields
- IEC 61000-4-8 Power frequency magnetic field immunity test
- IEC 61000-4-11 Voltage dips, short interruptions, and voltage variations immunity tests
|
Line Distortion |
EN 61000-3-2 per EMC Directive 89/336/EEC |
Voltage Fluctuations and Flicker |
EN 61000-3-3 per EMC Directive 89/336/EEC |
Dimensions
and Weights |
Chassis Height |
838.49mm (33.01 in) - 19 RU minus clearance |
Chassis Width |
444.5mm (17.50 in) |
Chassis Depth |
Includes chassis metal and front bezel:722mm (28.43 in)
In rack, distance from front vertical mounting rail to rear of chassis:700mm (27.56 in) |
Weight |
Fully configured system 243.13kg (536lbs)
Empty Chassis:11.34kg (94lbs) |
Rack
Mounting |
Chassis=19U / 2 chassis max per 42U rack. |