Processor |
Number |
M9000-32 SPARC64 VI: Up to 32 CPUs (64 Cores)
M9000-32 SPARC64 VII: Up to 32 CPUs (128 Cores)
M9000-64 SPARC64 VI: Up to 64 CPUs (128 Cores)
M9000-64 SPARC64 VII: Up to 64 CPUs (256 Cores) |
Architecture |
SPARC64 VI: 2.28GHz and 2.4GHz SPARC V9, ECC protected
SPARC64 VII: 2.52GHz SPARC V9, ECC protected |
Cache memory |
SPARC64 VI: 6MB Shared Level 2 on Chip Cache per Processor, 128KB
I-Cache and 128KB D-Cache Level 1 per Core
SPARC64 VII: 6MB Shared Level 2 on Chip Cache per Processor, 64KB I-Cache and 64KB D-Cache Level 1 per Core
|
System
Boards |
CPU/Memory Units (CMU) |
M9000-32: Up to 8
M9000-64: Up to 16 |
I/O |
M9000-32: Up to 16 External I/O Expansion
Units
M9000-64: Up to 16 External I/O Expansion Units |
eXtended System Control Facility Unit (XSCFU) |
M9000-32: 2
M9000-64: 4 |
Maximum Number of Domains |
24 |
Main
Memory |
M9000-32: Maximum 2TB using 8GB DIMMs, 256
DIMM slots
M9000-64: Maximum 4TB using 8GB DIMMs, 512 DIMM slots |
Standard
Interfaces |
Ethernet |
2 &215; 10/100 XSCF-LAN Ports per XSCFU |
PCI Express |
M9000-32: 64 Slots, expandable up to 224 Slots, via
optional external I/O Expansion Units
M9000-64: 128 Slots, expandable up to 288 Slots, via optional external
I/O Expansion Units |
Serial |
1 RJ-45 per XSCFU |
USB |
1 port per XSCFU that a field engineer can use to download
hardware information |
Internal
Mass Storage |
Disks |
M9000-32: Up to 32 disks, 4 per I/O Unit
M9000-64: Up to 64 disks, 4 per I/O Unit |
DVD-ROM |
1 per cabinet |
Tape |
1 Optional DAT72 Tape Drive per cabinet |
Power
Supplies |
M9000-32: 15 Power Supply Units (PSU) M9000-32 Base
M9000-64: 30 Power Supply Units (PSU) M9000-64 Base |
Environment
|
AC power |
200 to 240 VAC, 50-60Hz |
Power Consumption |
M9000-32: 21.3 kW (8 CMUs and 8 IOUs installed)
M9000-64: 42.6 kW (16 CMUs and 16 IOUs installed) |
Apparent Power |
M9000-32: 22.4 kVA (8 CMUs and 8 IOUs installed)
M9000-64: 44.8 kVA (16 CMUs and 16 IOUs installed) |
Power Factor |
0.9 or higher |
Rush Current |
100A0-p or less (current for each cable) |
Leak Current |
30mA or less |
Heat output (cooling requirement) |
See Sun SPARC Enterprise M8000/M9000 Servers Site Planning Guide (819-4203) |
There are a number of different power options available for
the M9000. For more specific details on the specifications related to them,
please see the Sun SPARC Enterprise M8000/M9000 Servers Site Planning Guide (819-4203). |
Power cords |
See Sun SPARC Enterprise M8000/M9000 Servers Site Planning Guide (819-4203). |
Temperature |
Operating:
Altitude 0 to less than 1500 Meters (0 - 4920 ft): 5° C to 32°
C ( 41° F to 89.6° F)
Altitude 1500 to less than 2000 Meters (4921 - 6561 ft): 5°
C to 30° C ( 41° F to 86° F)
Altitude 2000 to less than 2500 Meters (6562 - 8201 ft): 5°
C to 28° C ( 41° F to 82.4° F)
Altitude 2500 to less than 3000 Meters (8202 - 9843 ft): 5°
C to 26° C ( 41° F to 78.8° F)
Nonoperating: 0° C to 50° C ( 32° F to 122° F) |
Humidity |
Operating: 20% to 80% relative humidity, noncondensing
Nonoperating: 8% to 80% relative humidity, noncondensing |
Altitude |
Up to 3000M (9843 ft) |
Regulations
Meets or exceeds the following requirements: |
Safety |
CSA/UL-60950, EN60950, IEC950 CB Scheme with all national
deviations |
RFI/EMI |
EN55022/CISPR22 Class A, FCC CFR47 Part 15 Class A, EN61000-3-2,
EN61000-3-3 |
Immunity |
EN55024, EN61000-4-2, -4-3. -4-5. -4-6, -4-8, and -4/11 |
Regulatory Markings |
CE, FCC, ICES, C-tick, VCCI, GOST-R, BSMI, MIC, CSA/UL |
RoHS Compliance Level |
RoHS:YL |
Other Marks |
WEEE and China RoHS |
Dimensions
and Weights |
Height |
M9000-32: 180 cm (70.9 in)
M9000-64: 180 cm (70.9 in) |
Width |
M9000-32: 85 cm (33.5 in)
M9000-64: 167.4 cm (65.9 in) |
Depth |
M9000-32: 126 cm (49.6 in)
M9000-64: 126 cm (49.6 in) |
Weight |
M9000-32: 940 kg (2072 lbs)
M9000-64: 1880 kg (4145 lbs) |
Clearance
and Service Access |
Front |
90cm (35.4 in) |
Rear |
90cm (35.4 in) |
For more information, see the Sun SPARC Enterprise M8000/M9000 Servers Site Planning Guide (819-4203). |