Sun Microsystems, Inc.   Sun System Handbook - ISO 3.4 June 2011 Internal/Partner Edition
   Home | Current Systems | Former STK Products | EOL Systems | Components | General Info | Search | Feedback

Sun SPARC® Enterprise M9000 Server: Hardware Specifications


Processor
Number M9000-32 SPARC64 VI: Up to 32 CPUs (64 Cores)
M9000-32 SPARC64 VII: Up to 32 CPUs (128 Cores)
M9000-64 SPARC64 VI: Up to 64 CPUs (128 Cores)
M9000-64 SPARC64 VII: Up to 64 CPUs (256 Cores)
Architecture SPARC64 VI: 2.28GHz and 2.4GHz SPARC V9, ECC protected
SPARC64 VII: 2.52GHz SPARC V9, ECC protected
Cache memory SPARC64 VI: 6MB Shared Level 2 on Chip Cache per Processor, 128KB I-Cache and 128KB D-Cache Level 1 per Core
SPARC64 VII: 6MB Shared Level 2 on Chip Cache per Processor, 64KB I-Cache and 64KB D-Cache Level 1 per Core
System Boards
CPU/Memory Units (CMU) M9000-32: Up to 8
M9000-64: Up to 16
I/O M9000-32: Up to 16 External I/O Expansion Units
M9000-64: Up to 16 External I/O Expansion Units
eXtended System Control Facility Unit (XSCFU) M9000-32: 2
M9000-64: 4
Maximum Number of Domains 24
Main Memory
M9000-32: Maximum 2TB using 8GB DIMMs, 256 DIMM slots
M9000-64: Maximum 4TB using 8GB DIMMs, 512 DIMM slots
Standard Interfaces
Ethernet 2 &215; 10/100 XSCF-LAN Ports per XSCFU
PCI Express M9000-32: 64 Slots, expandable up to 224 Slots, via optional external I/O Expansion Units
M9000-64: 128 Slots, expandable up to 288 Slots, via optional external I/O Expansion Units
Serial 1 RJ-45 per XSCFU
USB 1 port per XSCFU that a field engineer can use to download hardware information
Internal Mass Storage
Disks M9000-32: Up to 32 disks, 4 per I/O Unit
M9000-64: Up to 64 disks, 4 per I/O Unit
DVD-ROM 1 per cabinet
Tape 1 Optional DAT72 Tape Drive per cabinet
Power Supplies
M9000-32: 15 Power Supply Units (PSU) M9000-32 Base
M9000-64: 30 Power Supply Units (PSU) M9000-64 Base
Environment
AC power 200 to 240 VAC, 50-60Hz
Power Consumption M9000-32: 21.3 kW (8 CMUs and 8 IOUs installed)
M9000-64: 42.6 kW (16 CMUs and 16 IOUs installed)
Apparent Power M9000-32: 22.4 kVA (8 CMUs and 8 IOUs installed)
M9000-64: 44.8 kVA (16 CMUs and 16 IOUs installed)
Power Factor 0.9 or higher
Rush Current 100A0-p or less (current for each cable)
Leak Current 30mA or less
Heat output (cooling requirement) See Sun SPARC Enterprise M8000/M9000 Servers Site Planning Guide (819-4203)
There are a number of different power options available for the M9000. For more specific details on the specifications related to them, please see the Sun SPARC Enterprise M8000/M9000 Servers Site Planning Guide (819-4203).
Power cords See Sun SPARC Enterprise M8000/M9000 Servers Site Planning Guide (819-4203).
Temperature Operating:
Altitude 0 to less than 1500 Meters (0 - 4920 ft):
5° C to 32° C ( 41° F to 89.6° F)
Altitude 1500 to less than 2000 Meters (4921 - 6561 ft): 5° C to 30° C ( 41° F to 86° F)
Altitude 2000 to less than 2500 Meters (6562 - 8201 ft): 5° C to 28° C ( 41° F to 82.4° F)
Altitude 2500 to less than 3000 Meters (8202 - 9843 ft): 5° C to 26° C ( 41° F to 78.8° F)
Nonoperating: 0° C to 50° C ( 32° F to 122° F)
Humidity Operating: 20% to 80% relative humidity, noncondensing
Nonoperating: 8% to 80% relative humidity, noncondensing
Altitude Up to 3000M (9843 ft)
Regulations
Meets or exceeds the following requirements:
Safety CSA/UL-60950, EN60950, IEC950 CB Scheme with all national deviations
RFI/EMI EN55022/CISPR22 Class A, FCC CFR47 Part 15 Class A, EN61000-3-2, EN61000-3-3
Immunity EN55024, EN61000-4-2, -4-3. -4-5. -4-6, -4-8, and -4/11
Regulatory Markings CE, FCC, ICES, C-tick, VCCI, GOST-R, BSMI, MIC, CSA/UL
RoHS Compliance Level RoHS:YL
Other Marks WEEE and China RoHS
Dimensions and Weights
Height M9000-32: 180 cm (70.9 in)
M9000-64: 180 cm (70.9 in)
Width M9000-32: 85 cm (33.5 in)
M9000-64: 167.4 cm (65.9 in)
Depth M9000-32: 126 cm (49.6 in)
M9000-64: 126 cm (49.6 in)
Weight M9000-32: 940 kg (2072 lbs)
M9000-64: 1880 kg (4145 lbs)
Clearance and Service Access
Front 90cm (35.4 in)
Rear 90cm (35.4 in)
For more information, see the Sun SPARC Enterprise M8000/M9000 Servers Site Planning Guide (819-4203).

  Copyright � 2011 Sun Microsystems, Inc.  All rights reserved.
 Feedback