Capacity |
Number |
- Up to 20 optional, hot-pluggable PCI ExpressModules (EM).
- Up to 2 optional, hot-pluggable PCI Express Network Express Modules (NEM).
- Up to 10 hot-pluggable Sun Netra Server Modules.
- 2 (N+1), hot-plug / hot-swap power supplies with independently wired fans.
- 2 Front Fan Modules (6 fans total).
- 6 Rear Fan Modules (12 fans total, N + 1 redundancy)
- One Chassis Monitoring Module (CMM).
|
Management Environment
|
Sun Netra 6000 Chassis Monitoring Module (CMM) |
-
Sun Netra 6000 chassis-level management is provided by the CMM's Integrated Lights-Out Management (ILOM) software.
ILOM 3.0.6.11 is the minimum supported firmware version.
- Management can be integrated into Sun and/or third-party management tools.
- Two ways to connect to CMM ILOM:
-
Connect a terminal or terminal emulation software to the SER MGT (RJ-45) port of the CMM to telnet into CMM ILOM.
-
Connect to the NET MGT 0 (10/100Base T ethernet) port of the CMM for Secure Shell (SSH) client access to CMM ILOM.
|
Power Supplies |
Number |
Two, hot-plug / hot-swap, high-efficiency(~90%) power supplies are provided in a N+1 redundant configuration.
|
Output |
AC: 5600-Watt per power supply.
DC: 2500-Watt per power supply |
AC / DC Input Connection |
- Americas/domestic: NEMA L6-20P to IEC 320-C19.
- International: IEC 309, 250 V, 16 A, 3Pin to IEC 320-C19.
- DC input connection is lug and post. See Install Guide for specifications.
|
Standard Integrated Interfaces |
Network |
The Sun Netra 6000, without an optional EM or NEM, does not offer production network or I/O connectivity.
|
I/O Interfaces |
The Sun Netra 6000 Modular System I/O is architected using PCI Express technology. I/O is offered in two form factors: PCI Express ExpressModules (EM) and PCI Express Network Express Modules (NEM).
|
Environment |
Airflow Requirements |
- Airflow (maximum) airflow inlet/outlet rate):1012 CFM (Cubic Feet per Minute).
- Airflow (typical): 600 CFM (Cubic Feet per Minute).
- Airflow direction: Front to rear.
|
Temperature |
Operating: 5°C to 45°C (41° F to 113° F).
Nonoperating: -40°C to 70°C (-40° F to 158° F).
Optimum ambient temperature: <22° C (71.60° F).
|
Relative Humidity |
Operating: 5% to 85% RH, non-condensing not to exceed 0.024kg Short Term.
Nonoperating: 93%, non-condensing, 38° C max wet bulb.
|
Altitude |
Operating:0 to 6,000 feet (1,800m), max. at aisle ambient temperatures of 45°C.
Nonoperating: Up to 39,370 feet (12,000m). |
Acoustic Noise |
LwAd (1 B = 10 dB) 7.5 B at or below 25°C, 9.2 B at max. ambient. |
Sine Vibration |
Operating: Z (vertical)-axis: 0.15G X/Y axis: 0.10G 5 to 500 Hz sine.
Nonoperating: Z (vertical)-axis: 0.50G X/Y axis: 0.25G 5 to 500 Hz sine.
|
Shock |
3Gs, 11msec, half sine (applied to rackmounted enclosure).
|
Regulations
|
NEBS Compliance Level |
NEBS Level 3 Certification |
RoHS Compliance Level |
RoHS:YL |
Product Safety |
- Product safety: UL/CSA 60950-1, EN 60950-1, IEC 60950-1 CB Scheme with all
country differences, IEC 825-1, 2, CFR 21 Part 1040, CNS 14336, GB 4943.
- Other: Labeled per WEEE (Waste Electrical and Electronic Equipment) Directive, China RoHS Mark.
|
Dimensions
and Weights |
Chassis Height |
AC Chassis: 438.15mm (17.25 in) - 10 RU minus clearance.
DC Chassis: 1 RU, or 1.75" taller than the DC Chassis Height. |
Chassis Width |
444.5mm (17.50 in). |
Chassis Depth |
692.15mm (27.25 in). |
Chassis Depth (in rack) |
27.25 inches (692 mm) (distance from front vertical mounting rail to rear of the chassis). |
Weight |
Fully configured system 160kg (350 lbs).
Empty Chassis:35.7kg (78.7lbs). |
Rack
Mounting |
AC Chassis=10R / 4 chassis max per 42U rack.
DC Chassis=11R / 3 chassis max per 42U rack. |