How to Remove and Replace a Sun Fire X4270 Fan Module
Related Categories |
- PLA-Support>Sun Systems>Sun_Other>Sun Collections>SN-OTH: x64-CAP VCAP
|
In this Document
Applies to:
Sun Fire X4270 Server - Version Not Applicable and later
Information in this document applies to any platform.
Goal
How to Remove and Replace a Sun Fire X4270 Fan Module
Fix
DISPATCH INSTRUCTIONS
WHAT SKILLS DOES THE ENGINEER NEED:(IS A SITE ENGINEER AVAILABLE?)
Familiarity or training for X4270 platform.
Procedure is documented in the Platform Service Manual 820-5830-13, Section 3.3
DELIVERY REQUIREMENT: Schedule with maintenance window within contractual terms.
TIME ESTIMATE: 20 minutes
FIELD ENGINEER INSTRUCTIONS
WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? :
Caution 1: If you remove one of the fans in the back row, replace it within 30 seconds to prevent overheating of the server.
Caution 2: Hazardous moving parts. Unless the power to the server is completely shut down, the only service permitted in the fan compartment is the replacement of the fan modules.
Note 1: Close the top cover door within 60 seconds to maintain adequate airflow to properly cool the server. Leaving the door open for more than 60 seconds, while the server is running, might cause the server to overheat and shut down
WHAT ACTION DOES THE ENGINEER NEED TO TAKE:
Remove a Fan Module
1. Prepare for servicing:
a. Attach an antistatic wrist strap.
b. Extend the server to the maintenance position.
2. Identify the faulty fan module with a corresponding Service Action Required LED.
3. Using your thumb and forefinger, grasp the handle on the fan module and lift it out of the server.
Caution 1: When removing a fan module, do not rock it back and forth. Rocking the fans modules can cause damage to the fan board connectors.
Caution 2: When changing the fan modules, note that only the fan modules can be removed or replaced. Do not service any other components in the fan compartment unless the system is shut down and the power cords are removed.
Install a Fan Module
1. Unpack the replacement fan module and place it on an antistatic mat.
2. Install the replacement fan module into the server.
The fan modules are keyed to ensure that they are installed in the correct orientation.
3. Apply firm pressure to fully seat the fan module.
4. Verify that the Service Action Required LED on the replaced fan module is not lit.
5. Verify that the Top Fan LED and the Service Action Required LED on the front of the server are not lit.
Note - If you are replacing a fan module when the server is powered down, the LEDs might stay lit until power is restored to the server and the server can determine that the fan module is functioning properly.
OBTAIN CUSTOMER ACCEPTANCE
WHAT ACTION DOES THE CUSTOMER NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE:
Restart system and have the System administrator verify functionality of system.
PARTS NOTE:N/A
REFERENCE INFORMATION:
X4270 Service Manual: