How to Replace a Sun Fire T1000 Server Fan Tray:ATR:1333621.1:0
Related Items |
- Sun SPARC Enterprise T1000 Server
- Sun Fire T1000 Server
|
Related Categories |
- PLA-Support>Sun Systems>Sun_Other>Sun Collections>SN-OTH: SPARC-CAP VCAP
|
In this Document
Applies to:
Sun Fire T1000 Server - Version Not Applicable to Not Applicable [Release N/A]
Sun SPARC Enterprise T1000 Server - Version Not Applicable and later
Information in this document applies to any platform.
Goal
How to Replace a Sun Fire T1000 Server Fan Tray
Fix
DISPATCH INSTRUCTIONS
WHAT SKILLS DOES THE ENGINEER NEED:(IS A SITE ENGINEER AVAILABLE?)
T1000 training recommended but not required (this is a CRU procedure).
TIME ESTIMATE: 30 minutes
TASK COMPLEXITY: 0
FIELD ENGINEER INSTRUCTIONS
WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? :
The customer should conduct an orderly software and system shutdown.
System power off is required.
WHAT ACTION DOES THE ENGINEER NEED TO TAKE:
1. Ensure system is shut down
2. Follow instructions in chapter 4 (Sun Fire T1000 Server Service Manual) to prepare the system for service.
The chassis cover might be very difficult to remove. If you press too hard on the cover lock button, the front edge of the cover might warp and bind. Also, elastic gasket material on the sides of the chassis might prevent the cover from sliding freely.
To work around this, lightly hold down the cover lock button and push the cover slightly toward the front of the chassis (this assists the unlocking action), then slide the cover approximately one half inch (12 mm) toward the rear of the chassis. You can now lift the cover off the chassis.
3. Disconnect the fan power cable from the motherboard.
4. Push in on the clasps on both sides of the fan assembly
5. Remove the fan assembly from the sheet metal mounting brackets.
6. Unpack the replacement fan tray assembly and place it on an antistatic mat.
7. Align the fan tray assembly with the sheet metal mounting brackets and slide it into place until the clasps on each side lock it into place.
8. Reconnect the fan power cable to the motherboard.
9. Follow instructions in Chapter 6 (Sun Fire T1000 Server Service Manual) to finish up hardware servicing.
OBTAIN CUSTOMER ACCEPTANCE
WHAT ACTION DOES THE CUSTOMER NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE:
Power on the server.
PARTS NOTE:
541-0582
REFERENCE INFORMATION:
Sun Fire T1000 Server Service Manual