Sun Microsystems, Inc.  Sun System Handbook - ISO 4.1 October 2012 Internal/Partner Edition
   Home | Current Systems | Former STK Products | EOL Systems | Components | General Info | Search | Feedback

Asset ID: 1-71-1332237.1
Update Date:2012-07-26
Keywords:

Solution Type  Technical Instruction Sure

Solution  1332237.1 :   How to remove and replace an x4275 Memory DIMM:ATR:1946:0  


Related Items
  • Sun Fire X4275 Server
  •  
  • Exadata Database Machine V2
  •  
Related Categories
  • PLA-Support>Sun Systems>Sun_Other>Sun Collections>SN-OTH: x64-CAP VCAP
  •  




In this Document
Goal
Fix


Applies to:

Sun Fire X4275 Server - Version Not Applicable and later
Exadata Database Machine V2 - Version Not Applicable and later
Information in this document applies to any platform.

Goal

Remove and replace x4275 Memory DIMM

Fix

CAP PROBLEM OVERVIEW: Faulty DIMM

DISPATCH INSTRUCTIONS

WHAT SKILLS DOES THE ENGINEER NEED:(IS A SITE ENGINEER AVAILABLE?)
No specific skills required

TIME ESTIMATE: 30 minutes

FIELD ENGINEER INSTRUCTIONS

WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? :

WHAT ACTION DOES THE ENGINEER NEED TO TAKE:

1. Powering off the system and disconnect the power cords from the system

2. Remove the top cover

3. Pressing the FAULT REMIND button to identify the location of the faulty DIMMs

4. remove the faulty DIMMs

5. Install the new DIMMs

6. Install the top cover

7. Connect the power cords and power on the system

8. Clear server DIMM faults

8-1. Confirm the server faults

-> Show /SP/faultmgmt

8-2. Clear the fault

-> set <Location> clear_fault_action=true

OBTAIN CUSTOMER ACCEPTANCE

WHAT ACTION DOES THE CUSTOMER NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE:

PARTS NOTE:

1.Install memory filler panel 350-1288 in all unused slots.

2.Install the first three DIMMs in CPU0 and CPU1 slots D8, D5, and D2.

3.Install the second three DIMMs in CPU0 and CPU1 slots D7, D4, and D1.

4.Use of the same DIMM size and speed is recommended for maximum performance.

REFERENCE INFORMATION:

Sun Fire X4170, X4270, and X4275 Servers Service Manual
http://download.oracle.com/docs/cd/E19871-01/820-5830-13/index.html


Attachments
This solution has no attachment
  Copyright © 2012 Sun Microsystems, Inc.  All rights reserved.
 Feedback