How to Replace a X4270 M2 Hard Disk Drive:ATR:2118:0
Related Categories |
- PLA-Support>Sun Systems>Sun_Other>Sun Collections>SN-OTH: x64-CAP VCAP
|
In this Document
Applies to:
Sun Fire X4270 M2 Server - Version Not Applicable and later
Information in this document applies to any platform.
Goal
How to Replace a X4270 M2 HDD
Fix
DISPATCH INSTRUCTIONS
WHAT SKILLS DOES THE ENGINEER NEED:(IS A SITE ENGINEER AVAILABLE?)
As required
Time Estimate: 30 minutes
TASK COMPLEXITY: 0
FIELD ENGINEER INSTRUCTIONS
WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? :
1. Identify the storage drive you wish to remove.
2. Determine whether the storage drive can be hot-plugged or cold-plugged.
3. You must power off the server, if the storage drive:
a. Contains the operating system, and the operating system is not mirrored on
another drive.
b. Cannot be logically isolated from the online operations of the server.
WHAT ACTION DOES THE ENGINEER NEED TO TAKE:
Removing the drive
1. Do one of the following:
a. To hot-plug a drive, unconfigure the storage drive, as required.
You must take the drive offline before you can safely remove it. This removes
the logical software links to the drive and prevents any applications from
accessing it.
b. To cold-plug a drive, you must power off the server before you can safely remove the storage drive.
2. On the drive you plan to remove, push the storage drive release button to open the latch.
3. Grasp the latch and pull the drive out of the drive slot.
Installing the drive
1. If necessary, remove the blank panel from the chassis: The server might have covering unoccupied storage drive slots.
2. Look for the slot you want to replace the drive.
3. Slide the drive into the drive slot until it is fully seated.
4. Close the latch to lock the drive in place.
5. If:
a. you have hot-plugged the drive, configure the storage drive.
b. you have cold-plugged the drive, restore power to the server .
OBTAIN CUSTOMER ACCEPTANCE
WHAT ACTION DOES THE CUSTOMER NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE:
System administrator verify functionality of system.
PARTS NOTE:
Caution: The latch is not an ejector. Do not bend it too far to the right. Doing so can
damage the latch.
Caution: Whenever you remove a storage drive, you should replace it with another
storage drive or a filler panel before you power on the server; otherwise the server
might overheat due to improper airflow.
REFERENCE INFORMATION
Sun Fire X4270 M2 Server Service Manual
http://download.oracle.com/docs/cd/E19245-01/
Detailed SVM instructions can be found at:
http://download.oracle.com/docs/cd/E19253-01/816-4520/troubleshoottasks-96/index.html
See Document 1010946.1 for Detailed Veritas Volume Manager instructions.
See Document 1002753.1 for Detailed ZFS instructions