Solution Type Technical Instruction Sure Solution 1302011.1 : How to Replace a X4640 Fan Module:ATR:1841:1
In this Document
Applies to:Sun Fire X4640 Server - Version: Not ApplicableInformation in this document applies to any platform. GoalHow to remove and replace a X4640 Fan ModuleSolutionDISPATCH INSTRUCTIONSWHAT SKILLS DOES THE ENGINEER NEED:(IS A SITE ENGINEER AVAILABLE?) No specific skills required DELIVERY REQUIREMENT: As scheduled TIME ESTIMATE: 30 minutes FIELD ENGINEER INSTRUCTIONS WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? : System shutdown is not required. This component is a hot-swappable CRU WHAT ACTION DOES THE ENGINEER NEED TO TAKE: 1. Identify the Fan Module (FT1- FT4) which requires replacement Refer to the Service Manual for the specific position of Fan. 2. Remove the Fan Module from the chassis Pinch both plastic securing buttons toward the center of the fan tray, and simultaneously lift the fan tray up and out of the chassis 3. Insert the new Fan Module into the chassis within 60 seconds after removal of the faulty fan module. * Failure to insert the fan within 60 seconds will result on the machine powering off * Push down gently until the connector is fully engaged and the plastic securing buttons snap into place. OBTAIN CUSTOMER ACCEPTANCE WHAT ACTION DOES THE CUSTOMER NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE: PARTS NOTE: Refer to the Service Manual for the specific position of Fan REFERENCE INFORMATION: - Service Manual http://download.oracle.com/docs/cd/E19273-01/ Attachments This solution has no attachment |
||||||||||||
|