Solution Type Technical Instruction Sure Solution 1014160.1 : SL8500 - Power Failure Troubleshooting Process
PreviouslyPublishedAs 220498 Applies to:Sun StorageTek SL8500 Modular Library System - Version Not Applicable and laterAll Platforms Checked for relevance on 27-July-2012. GoalHow to trouble shoot power failure: Internal power loss Internal power failure Power missing FixResolution 1. Standard AC power grid (N+1 configuration). 2. Optional second (redundant) AC power grid - 2N configuration. 3. DC power grid for tape drive bus operation contains the following DC power supplies: PS,AC/DC,+48VG,24A,+12V,4A,1200W. 4. DC power grid for HandBot bus operation contains the following DC power supplies: PS,AC/DC,+48VG,24A,+12V,4A,1200W. 5. DC power grid for customer interface module components (elevator, turntables, service safety door, OP Panel and CAPs) contains the following DC power supplies: PS,AC/DC,+48VG,24A,+12V,4A,1200W. If the effected areas are contained within the above identified DC grids (items 3, 4, or 5), suspect the controlling power supplies are failing.
DC power grid for TAPE DRIVE bus operation contains the following DC power supplies: WITH N+1 POWER - 1,2,3,4,7,8,13,14,19,20. WITH 2N POWER - 1,2,3,4,7,8,9,10,13,14,15,16,19,20,21,22. DC power grid for HandBot bus operations contains the following DC power supplies: WITH N+1 POWER - 5,6,11,12,17,18. WITH 2N POWER - 5,6,11,12,17,18,23,24. DC power grid for CUSTOMER INTERFACE MODULE bus operation contains the following DC power supplies: WITH N+1 POWER - 25, 26. WITH 2N POWER - 25, 26. Attachments This solution has no attachment |
||||||||||||
|