Solution  1490235.1 :   HARDWARE FAULT: Component Error Detected. Component Name: /SYS/TEMP_ATTN  


Related Items
  • Exadata Database Machine X2-2 Qtr Rack
  •  
Related Categories
  • PLA-Support>Sun Systems>SAND>Network>SN-SND: Sun Network Infiniband
  •  




In this Document
Symptoms
Cause
Solution


Created from <SR 3-6184725510>

Applies to:

Exadata Database Machine X2-2 Qtr Rack - Version Not Applicable and later
Information in this document applies to any platform.

Symptoms

 [sw-ib3 ~]# env_test

Starting Temperature test:
Back temperature 39 <--------Cold isle Celcius
Front temperature 40<--------Warm isle Celcius
WARNING SP temperature 61 too high <---------------Temperature too high
Switch temperature 52, maxtemperature 53
Temperature test returned 1 faults

Cause

Data center experienced an air conditioning failure

Solution

Customer repaired the datacenter air conditioning.

Starting Temperature test:
Back temperature 34
Front temperature 35
SP temperature 51
Switch temperature 50, maxtemperature 57
Temperature test returned OK

 