Solution Type Problem Resolution Sure Solution 1413450.1 : SL500 - CAP Not Opening
In this Document Created from <SR 3-5003251287>
Applies to:Sun StorageTek SL500 Modular Library System - Version: Not ApplicableInformation in this document applies to any platform. SymptomsBase Module CAP not opening. All other library operations are normal.CAP remains closed after open command & pressing eject button. CAP LED does glow. FE Cleaned & adjusted CAP sensor, re-fixed the CAP sensor to RLM card interconnect cable. FE confirmed the CAP door is physically closed firmly but BM CAP Door Sensor status is OPEN. -------------- CAP Door Sensors: Module 1: OPEN Module 2: CLOSED Module 3: CLOSED ----------- 'diagcaps' from CLI fails with below error: ----------- SERVICE>> diagcaps SERVICE>> Press the CAP Open button on the Key Pad. SERVICE>> Diagnostic Failed SERVICE>> cause: (3559CAP Open LED Failure: LED should be on) ------- -- Error from SL500 Event Logs--- 2011-12-01T05:12:10.403, 0.0.0.0.0, 3200, ifm, error, 3000, 3320, "(request id = OpelServer/0x7ffffc80) IfmMove::prepareForMove():destination location: (LMRC) 0,1,1,8 CAP is NOT CLOSED" CauseThis SL500 was a new install and cable damage is suspected.SolutionEnsure the Interconnect Cable between RLM card and CAP Sensor is seated correctly and in the J110 connector on RLM.2 parts were replaced to fix the problem: 314562302 [F] CBL ASSY,RLM-SWITCH,CAP 314562301 [F] 419650101 [F] CBL ASSY,CAP 314504201 [F] Attachments This solution has no attachment |
||||||||||||
|