Sun Microsystems, Inc.  Sun System Handbook - ISO 4.1 October 2012 Internal/Partner Edition
   Home | Current Systems | Former STK Products | EOL Systems | Components | General Info | Search | Feedback

Asset ID: 1-72-1365587.1
Update Date:2011-10-10
Keywords:

Solution Type  Problem Resolution Sure

Solution  1365587.1 :   SL8500 - Result Code 1321 - Failure From Power Supply - Address: 1  


Related Items
  • Sun StorageTek SL8500 Modular Library System
  •  
Related Categories
  • PLA-Support>Sun Systems>TAPE>Tape Hardware>SN-TP: SL3000-8500 Library
  •  




In this Document
  Symptoms
  Changes
  Cause
  Solution
  References


Oracle Confidential (PARTNER). Do not distribute to customers
Reason: Confidential for Oracle Support personnel

Created from <SR 3-4685386731>

Applies to:

Sun StorageTek SL8500 Modular Library System - Version: Not Applicable and later   [Release: N/A and later ]
Information in this document applies to any platform.

Symptoms

Customer reported multiple drives intermittently going offline.

The library error warn info event log does not show any drive load/unload errors.
Instead, the library event log shows errors like this:
Time : 2011-09-26T13:13:11.212
Device Address : 1.0.0.1.26
User : root
Requester : default
Activity : queryLibrary
Request Id : 2848901
Level : error
Result Code : 1321
Text : "Failure from power supply - Address: 1
Parameters : 0,0,1,26 - Status: (PowerFail: true)(present: true)(24v_ok: false)(pha_bo: false)(phb_bo: false)(phc_bo: false)(pha_pres: false)(phb_pres: false)(phc_pres: false)"

RC1321
Error 1321
The library event log is reporting problems with 3 power supply components:
1. Power_Supply_Rail_AC2N+1(1.0.0.1.17)
2. Power_Supply_HBZ_26(1.0.0.1.26)
3. Power_Supply_ECM_PS2_AC2(1.0.0.1.28)
 

Changes

No known changes

Cause

Power supply 1.0.0.1.17, 1.0.0.1.26, and 1.0.0.1.28 draw power from AC 2 PDU.

DC power supply 1.0.0.1.17 supplies power to some tape drives.  If not enough power is going to the drives,
the drives may go offline.

Solution

1. Ask the customer to check the outside AC power source. See if there is a problem.

2. If there is no problem with the data-center's power source, check the AC 2 PDU. It may have tripped.
    Replace the AC2 PDU if there is a problem.

3. If there is no problem with the AC 2 PDU, check if there are problems with:
    Power_Supply_Rail_AC2N+1(1.0.0.1.17)
    Power_Supply_HBZ_26(1.0.0.1.26)
    Power_Supply_ECM_PS2_AC2(1.0.0.1.28)
    Replace as needed.
 

References

<NOTE:1365634.1> - SL8500 - How to remove and replace the PDU

Attachments
This solution has no attachment
  Copyright © 2012 Sun Microsystems, Inc.  All rights reserved.