Solution Type Problem Resolution Sure Solution 1319438.1 : SL8500 - Rail Communication Problems May Cause Multiple Robot Failures on the Same Rail
In this Document
Applies to:Sun StorageTek SL8500 Modular Library System - Version Not Applicable and laterInformation in this document applies to any platform. Checked for relevance on 10-Oct-2012. SymptomsRepeating H-Bot failures on the same rail. CausePossible rail communication problem. Terminators are the most likely cause for poor rail communications but it can also be caused by a faulty HBS card, or rarely, copper strip contamination. SolutionStats Network Command Useful - Do not overlook rail communication problems any time multiple bot failures occur on any rail. The easiest way to display the communication statistics is to issue the "stats network" command at the CLI. Look for errors, frames and drops. Normally these number should be in the 1 to 4 digit range depending on when the library was last booted. Any of these numbers in the 5+ digit range are cause for concern. At no time should the errors be more than 5% of the received packets. Typical numbers are below 1%. Contact Tape Hardware Support for additional help as needed. Attachments This solution has no attachment |
||||||||||||||||
|