Solution Type Problem Resolution Sure Solution 1020584.1 : POST Fails on 6120/6920/6320 array configuration with "Vcc Differential mode test failed"
PreviouslyPublishedAs 261188 Applies to:Sun Storage 6120 Array - Version Not Applicable and laterSun Storage 6320 System - Version Not Applicable and later Sun Storage 6920 System - Version Not Applicable and later All Platforms ***Checked for relevance on 11-June-2012*** SymptomsIssue presents Itself with the following symptoms:
At this point:
After manual intervention the controller continues to boot. CauseThis is an issue with the Power Cooling Unit (PCU). SolutionResolution requires replacement of BOTH PCU in the tray with the faulted controller. Attachments This solution has no attachment |
||||||||||||
|