Solution  1310393.1 :   How to replace a V245 System Fan Tray:ATR:1259:0  


Related Items
  • Sun Fire V245 Server
  •  
Related Categories
  • GCS>Sun Microsystems>CAP VCAP
  •  




In this Document
  Goal
  Solution


Applies to:

Sun Fire V245 Server - Version: Not Applicable and later   [Release: N/A and later ]
Information in this document applies to any platform.

Goal

How to replace a V245 System Fan Tray

Solution

*DISPATCH INSTRUCTIONS*

WHAT SKILLS DOES THE ENGINEER NEED:(IS A SITE ENGINEER AVAILABLE?)
No specific skills required

DELIVERY REQUIREMENT:
As scheduled

*FIELD ENGINEER INSTRUCTIONS*

PROBLEM OVERVIEW:
Faulty Fan

WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? :

A data backup is not a pre-requisite but is a wise precaution.
The customer is not required to perform a system shutdown.

WHAT ACTION DOES THE ENGINEER NEED TO TAKE:

1. Determine which fan tray needs to be removed
The following indicators are lit when a fan tray fault is detected:
Front and rear Service Required indicators
Top Fan indicator on the front of the server
Fan Fault indicator on the faulty fan
2. Open the appropriate fan tray door
A lit Fan Fault indicator on the top of a fan tray indicates that the fan tray is faulty
3. Pull up on the fan tray handle until the fan tray is removed from the chassis
4. Insert the new fan tray
5. Confirm that the new fan tray is working
The fay tray indicator should be green
6. Verify that the Fan Fault indicator on the replaced fan tray is not lit. Also
verify that the Top Fan indicator, Service Required indicators, and the Locator
indicator/Locator button are not lit
7. Close the fan tray door

(FIGURE 2-2).
2. Apply firm pressure to fully seat the fan tray.
4. Close the front cover door.
5. If necessary, return the server to its normal position in the rack.

WHAT ACTION DOES THE CUSTOMER NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE:

Check Fan tray LEDs

PARTS NOTE:

REFERENCE INFORMATION:

Service Manual.
http://download.oracle.com/docs/cd/E19088-01/

TIME ESTIMATE:

15 Minutes