Sun System Handbook - ISO 3.4 June 2011 Internal/Partner Edition | |||
|
|
Solution Type Technical Instruction Sure Solution 1015771.1 : SL8500 - Procedure to Reset and Calibrate Operator Panel
PreviouslyPublishedAs 224489 Oracle Confidential (PARTNER). Do not distribute to customers Reason: Confidential for Partners and Oracle Support personnel
Applies to:Sun StorageTek SL8500 Modular Library System - Version: Not Applicable and later [Release: N/A and later]All Platforms Checked for relevance on 8-Feb-2011. GoalProcedure to Reset and Calibrate Operator Panel on SL8500 Library.SolutionSteps to FollowUse the following procedures to reboot or re-calibrate the SL8500 Local Operator Panel Both procedures are exceptional procedures and should only be employed if needed. Power On Reset: Note: If your library does not contain a Service Safety Door, the procedure below is disruptive and requires you to take the library offline. If you open the Library front access doors without the Service Safety Door all the rails and HBZ module will power down. Note: It is also possible to non-disruptively access the power switch by removing the lower facade and reaching behind the left side of the Operator Panel but there is some risk of damaging the cables in this area and caution should be exercised. > Activate the Service Safety Door to the left. > Open the left access door. > Remove the access panel behind the lower left corner of the operator panel from inside the CIM to access the power switch on the back of the OP Panel. > Power-off, then-on the operator panel. Rebooting StreamLine Library Console using the Remote StreamLine Library Console: > In the Tools menu, click Diagnostics; menu options may vary with SLC versions below FRS_2.40. > Select the Activate Code tab. > In the target field, select SLConsole. > Select the active version of StreamLine Library Console, denoted by the asterisk on the left. > Click Activate > Click OK when the informational message appears. > A warning message will appear on your laptop screen before the reboot occurs. StreamLine Library Console will display BIOS information and will then reboot Windows 2000. > StreamLine Library Console will start and the login screen will re-appear. Calibration At SLC Boot Up: Note: Should be an exceptional procedure, all panels are calibrated in manufacturing and should not need recalibration in the field. > Power-off the operator panel. > Power-on the operator panel. > Carefully watch the screen. When the Windows desktop first appears, touch the screen; then, as soon as possible, close hand corner> of the black DOS screen. Note: If you do not close the DOS screen, the StreamLine Library Console application will activate within five seconds. > Look to the bottom right for a PM icon, touch this icon. > A menu will appear. > Select Control Panel. > Select the Calibrate tab. > When the window appears, select Calibrate again. > At the top of the blank screen, you will see the words Point here . > Touch the exact middle of the circle with a stylus. > Continue touching the exact middle of the circle as it moves to each location on the screen. > After all four screen-circle locations have been calibrated, click OK. > To initialize the StreamLine Library Console: a. Click Start in the lower left corner. b. Select Startup from the menu. c. Click SLConsole. Calibration Using Penmount Application: Note: Should be an exceptional procedure, all panels are calibrated in manufacturing and should not need recalibration in the field. > At the screen, touch Start > Programs > Penmount Utilities 2000 > > Penmount Control Panel > Select Calibrate > Perform steps noted above. @ Operator panel, SL8500, How to reboot local operator panel, How to recalibrate local operator panel, Procedure to reboot operator panel, Procedure to recalibrate operator panel, Procedure, Reset Op Panel, recalibrate, Calibrate Op Panel Previously Published As STKKB77069 Attachments This solution has no attachment |
||||||||||||
|