Sun System Handbook - ISO 3.4 June 2011 Internal/Partner Edition | |||
|
|
Solution Type Technical Instruction Sure Solution 1004381.1 : SL8500 - Information on PDU Phase LED's
PreviouslyPublishedAs 206057 Oracle Confidential (PARTNER). Do not distribute to customers Reason: Confidential for Partners and Oracle Support personnel
Applies to:Sun StorageTek SL8500 Modular Library SystemSun StorageTek SL8500 Modular Library System - Version: Not Applicable and later [Release: N/A and later] All Platforms Checked for relevance on 12-May-2011. GoalInformation on PDU Phase LED's:The SL8500 PDU Phase LED's which indicate all phases are present have been going out prematurely or found to be inoperative at the time of install. SolutionSteps to FollowThe SL8500 PDU Phase LED's which indicate all phases are present have been going out prematurely or found to be inoperative at the time of install.
SL8500 PDU Phase LED's
Note: All levels of PDU's are impacted and the PDU assembly part number is not scheduled to change but the internal PDU cards will be updated. Card PWA P/N (Old) PWA P/N (New) HBUD 313824404 313824505 HBUS 313966303 313966404 HBUY 313965303 313965404 Old PWB P/N: 313824103 New PWB P/N: 313824104 Old LED P/N: 15569031 New LED P/N: 260069274 EC: 142001 Engineering does not recommend the PDU assembly be replaced in the advent of an LED failure. Use the procedure below to determine if the input phases are correct: -Inspect all the AC to DC power supplies. All power supplies have a "Green LED" indicating AC voltage is present. Each phase handles 1/3 of the load, if a phase is missing approximately 1/3 of the supplies will indicate no AC present. Power Supplies: Power supplies 1 through 24 (drive and rail) SL8500 Modular Library System, SL8500, PDU Phase LED's, LED's, CRCM Previously Published As 90883 Attachments This solution has no attachment |
||||||||||||
|