Solution Type FAB (standard) Sure Solution 1000710.1 : Sun Fire 3800/4800/4810/6800 Servers may encounter power error issue when system RTS/RTU units are configured from a single power source.
PreviouslyPublishedAs 200928 Product Sun Fire 3800 Server Sun Fire 4800 Server Sun Fire 4810 Server Sun Fire 6800 Server Part
Impact This configuration can lead to a greater system interruption hazard during failover of the RTS than a single power source configured into a single RTU with one RTS connected. Contributing Factors Configuring a single source into 2 RTS units installed into the same RTU is not recommended by SUN. Symptoms Sun Fire Servers (3800/4800/4810/6800) may encounter power failover issues when system RTS/RTU units are configured from a single power source. This configuration can lead to a greater system interruption hazard during failover of the RTS than a single power source configured into a single RTU with one RTS connected.
There are no software commands for determining whether a system has an affected RTS or not. Please follow these steps to determine if a system or cabinet is affected:
A: Two independent sources of power connected to the RTU. B: One source of power connected to one RTS in a RTU with the other RTS either not installed or left disconnected.
http://www.sun.com/products-n-solutions/hardware/docs/pdf/817-2353-12.pdf
Root Cause
Workaround For Sun Fire 3800/4800/4810/6800 systems with a single source input connected to two RTS's in a single RTU box, bring the system into a supported configuration or inform the customer of the risks associated with 300-1396-05 (or below) RTS units.
http://www.sun.com/blueprints/0901/sunfireconfig.pdf RTS units are highly reliable. The possibility of a failover issue and an unplanned outage in the Single Source to Dual RTS configuration is actually greater than the possibility of an RTS failure causing an outage. Modification History Date: 05-OCT-2005
Previously Published As 101951 Internal Comments None Related Information
Internal Eng Business Unit Group KE Authors Internal Services Knowledge Engineer [email protected] Internal Kasp FAB Legacy ID 101951, I1133-1 (FIN) Internal Sun Alert & FAB Admin Info Critical Category: Significant Change Date: Avoidance: Workaround Responsible Manager: null Original Admin Info: [WF 05-10-2005, sean: I updated the document to include the correct URL and make a history note] [WF 30-Sep-2005, karened: sean updated the FIN according to feedback and then released via Send Direct. However we noticed the Legacy ID was not showing up in Preview. (it was showing up blank). I remembered how to fix it and then re-released] Product_uuid 29d05214-0a18-11d6-92b2-a111614865b5|Sun Fire 3800 Server 29d3a694-0a18-11d6-92da-df959df44cdd|Sun Fire 4800 Server 29d6f808-0a18-11d6-8aa8-943929fbbdd8|Sun Fire 4810 Server 29da7938-0a18-11d6-8a41-9ed1ad6d6779|Sun Fire 6800 Server Attachments This solution has no attachment |
||||||||||||
|