Sun Microsystems, Inc.   Sun System Handbook - ISO 3.4 June 2011 Internal/Partner Edition
   Home | Current Systems | Former STK Products | EOL Systems | Components | General Info | Search | Feedback

Sun Enterprise[tm] 10000 Server: Hardware Specifications

Processor
Number 4 to 64
Architecture 250, 336, 400, or 466 MHz UltraSPARC[tm]-II
Cache per processor Primary: 16-KB instruction, and 16-KB data on chip
Secondary: 4-MB external cache or 8-MB external cache (466 MHz module)
CPU interface 64-bit Ultra Port Architecture (UPA)
System Interconnect

Gigaplane-XB interconnect, 12.8 GB/second throughput
Memory data bus: 576 bits
Data bus: 144 bits per board
CPU data bus: 144 bits

System Boards
Number of boards Maximum of 16 boards per Enterprise 10000 server; minimum configuration is one system board
CPU/Memory board Up to four processors and four banks of eight memory SIMMs on each system board
I/O Board Up to four SBus cards or two PCI cards on each system board
Control Board Up to two boards per Enterprise 10000 server; controls the system JTAG, clock, fan, power, serial interface, and Ethernet interface functions
Main Memory

2-GB to 64-GB memory capacity per system

256-MB and 1-GB memory expansion options (each a group of 8 SIMMs)

Up to four memory expansion options per system board

Standard Interfaces
Ethernet One twisted-pair ethernet (10BASE-T) port (RJ-45) per Control Board; for use only between the Control Board(s) and the System Service Processor(s)
PCI Two slots per PCI I/O module mounted on the System Board; 32-bit or 64-bit data bus width, 33- or 66-MHz, short cards (6.5-inch)
SBus Four slots per SBus I/O module mounted on the System Board; 32-bit or 64-bit data bus width, 25 MHz
Internal Mass Storage
Disk Array/Tray

Maximum of two Sun StorEdge D1000 arrays (capacity up to 2 TB)
or

Maximum of 16 UniPack disks and 4 UniPack trays

or
a combination of both

Power Supplies

N+1 system redundancy
Universal 220 VAC-to-48 DC volt
up to 2 AC power sequencers

Environment
AC input1 200 - 240 VAC, 47 - 63 Hz, 24 A (max)
Input power 13,456 W
Heat output 52,000 BTU/hr
Temperature Optimal: 21° C to 23° C (70° F to 74° F)
Operating: 10° C to 32° C (50° F to 90° F)
Nonoperating: -40° C to 65° C (-40° F to 149° F)
Humidity2 Optimal: 45% to 50% relative humidity, noncondensing
Operating: 20% to 80% relative humidity, noncondensing
Nonoperating: Up to 93% relative humidity, noncondensing
Altitude Operating: 3000 m (10,000 ft.)
Nonoperating: 12,000 m (40,000 ft.)
Number of cords 5 (max)
1 Per line cord; up to five redundant line cords
2 Operating temperature ramp rate not to exceed 68° F (20° C) per hour, humidity ramp rate not to exceed 30% relative humidity per hour. Nonoperating temperature ramp rate not to exceed 59° F (15° C) per hour, humidity ramp rate not to exceed 20% relative humidity per hour.
Regulations
Meets or exceeds the following requirements:
Safety UL 1950, CUL CAN/CSA 22:2 M950, TUV EN60950
RFI/EMI FCC Class A, EN50021-1 Class A
Immunity EN50082-1
Dimensions and Weights
Height 177.8 cm (70 in.)
200 cm (78.75 in.) shipping
Width 97.2 cm (38.25 in.)
123.8 cm (48.75 in.) shipping
Depth 126.8 cm (49.9 in.)
155.6 cm (61.25 in.) shipping
Weight 909 kg (2000 lb.) approximate
1000 kg (2200 lb.) approximate shipping
Power Cord 4.6 m (15 ft.)
Clearance and Service Access
Front1 40.6 cm (16 in.)
Rear1 40.6 cm (16 in.)
1 If no peripheral is over 50.8 cm (20 in.); if a peripheral is over 50.8 cm (20 in.), add additional access space to accommodate the excess length.

  Copyright � 2011 Sun Microsystems, Inc.  All rights reserved.
 Feedback