Sun Microsystems, Inc.   Sun System Handbook - ISO 3.4 June 2011 Internal/Partner Edition
   Home | Current Systems | Former STK Products | EOL Systems | Components | General Info | Search | Feedback

Sun StorEdge[tm] 3511 FC Array: Hardware Specifications

250 GB Hitachi 250GB - 7200 RPM, SATA Disk Drive
400 GB Hitachi 400GB - 7200 RPM, SATA Disk Drive
500 GB Hitachi 500GB - 7200 RPM, SATA Disk Drive
Note 1: All RAID configurations ship pre-configured with RAID level zero (RAID 0).
Note 2: Supported RAID levels include 0, 1, 1+0, 3, 5, 3+0, and 5+0.
Up to 12 Disk drives per array
250GB Disk drives 12 x 250 = 3TB
400GB Disk drives 12 x 400 = 4.8TB
500GB Disk drives 12 x 500 = 6.0TB
Power Requirement AC: 90 to 264 VAC, single phase (47 to 63Hz)
DC: -36 to -75 VDC
Input Voltage AC: 100 to 240 VAC, single phase
DC: -48 to -60 VDC, 18A
Current Per Input AC: Values include:
  • 90 VAC (3.51A) to 264 VAC (1.25A), 50 Hz
  • 90 VAC (3.56A) to 264 VAC (1.31A), 60 Hz
DC: -48 to -60 VDC, 18A
Maximum Inrush Current 115 VAC: 50A peak
230 VAC: 100A peak
Power Supply Output Voltages +5VDC and +12VDC
Heat Output 1105 BTU/hr (fully populated array)
Altitude Operating: -30 m to 3,048 m(-100 to 10000 feet)
Non-operating: -30 m to 12192 m(-100 to 40000 feet)
Temperature Operating: 5° C to 40° C (41° F to 104° F)
Non-operating: -40° C to 65° C (-40° F to 149° F)
Humidity Operating: 10% to 90% relative to 27° C max. wet bulb, noncondensing
Non-operating:) 0% to 90% relative to 38° C max. wet bulb, noncondensing
Shock Operating: 5.0 G, 11-ms, half-sine
Non-operating: 15.0 G, 11-ms, half-sine
Vibration Operating: 0.2 G, 5-500 Hz, swept-sine
Non-operating: 1.0 G, 5-500 Hz, swept-sine
Height Desktop: 9.25 cm (3.64 in)
Rackmount: 8.89 cm (3.5 in)
Width Desktop: 48.26 cm (19 in)
Rackmount: 44.7 cm - body only (17.6 in)
Depth Main Chassis: 45.72 cm (18.0 in)
Chassis with Fan Modules: 50.80 cm (20.0 in)
Chassis with Fan Modules and Handles: 53.34 cm (21.5 in)
Weight Fully Loaded 26.8 kg (59.1 lbs)
Packaged Weight (fully loaded): 31.9 kg (70.5 lbs)
Safety UL listed CSA-C22.2 No. 60950-00, EN 60950:2000, IEC 60950, GS, GOST, S-Mark
Emission FCC Part 15 Class B, ICES-003, EN 300 386, EN55022 Class B, VCCI Class B, EN AS/NZS 3548 Class B, BSMI Class B
Harmonics EN 61000-3-2, EN 61000-3-3
Immunity EN300 386, EN 55024
Other NEBS Level 3 (GR-63-CORE; GR-1089-CORE), MIL-STD-810F, ETSI EN 300 019
Front 37 cm (15 in) service clearance, 15 cm (6 in) cooling clearance
Rear 37 cm (15 in) service clearance, 15 cm (6 in) cooling clearance
Airflow for cooling is from front to rear
Rack Mounting
Rack mountable in 19" wide rack

 


  Copyright � 2011 Sun Microsystems, Inc.  All rights reserved.
 Feedback